- The TUNING section allows for different calibration at two different pressure points
- Points marked 1 refer to the low pressure point while those marked 2 refer to the high pressure point
- To calibrate using this section, proceed as follows:
- Set pressure point 1 (in the example of the pictures 84bar)
- Then click on the button with the calculator, set the required power value and wait for the software to find the corresponding factor
- Then set the pressure of point 2 (in the example of the pictures 95bar)
- Then click on the button with the calculator, set the required power value and wait for the software to find the corresponding factor
- The same mechanism for power also applies to pressure drop